Table 91: Calculated voltages for different connection types
Voltage connection
Phase-to-phase
voltages (Ph-Ph)
Phase-to-neutral
voltages (Ph-n)
Residual voltage Uo
3 × ph-n
yes, calculated
yes
yes, calculated
3 × ph-n + Uo
yes, calculated
yes
yes
2 × ph-n
yes, calculated
1
yes, missing ph-n cal-
culated
1
no
2 × ph-n + Uo
yes, calculated
yes, missing ph-n cal-
culated
yes
3 × ph-ph
yes
yes, calculated
1
no
3 × ph-ph + Uo
yes
yes, calculated
yes
2 × ph-ph
yes, missing ph-ph
calculated
yes, calculated
1
no
2 × ph-ph + Uo
yes, missing ph-ph
calculated
yes, calculated
yes
3.12
Sensor inputs for currents and voltages
This chapter gives short examples on how to define the correct parameters for
sensor measurement interfaces.
Sensors can have correction factors, measured and verified by the sensor
manufacturer, to increase the measurement accuracy. Correction factors
are recommended to be set to the relay. Two types of correction factors
are available for voltage and current (Rogowski) sensors. The Amplitude
correction factor is named
Amplitude corr. A(B/C) and Angle correction
factor is named
Angle corr A(B/C). These correction factors can be found
on the Sensor's rating plate and/or sensor routine test protocol. If the
correction factors are not available, contact the sensor manufacturer for
more information.
Figure 56: Example of ABB Rogowski current sensor KECA 80 D85 rating plate
Current (Rogowski) sensor setting example
In this example, an 80 A/0.150 V at 50 Hz (0.180 V at 60 Hz) sensor, such as
the example shown in
, is used in a 50 Hz electrical network. The
application has a 150 A nominal current (In) corresponding to the protected
object’s nominal current. The application nominal current is set to Rogowski
1
Uo assumed zero.
1MRS759142 F
Basic functions
REX640
Technical Manual
157
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......