AC-POWER
Issue 4 May 2002
10-5
555-233-123
AC Power Query Test (#78)
Table 10-2.
TEST #78 AC Power Query Test
Error
Code
Test
Result
Description / Recommendation
1000
ABORT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5
times.
2000
ABORT
Response to the test request was not received within the allowable
time period.
1. Retry the command at 1-minute intervals a maximum of 5
times.
2. If the test continues to ABORT with Error Code 2000, check for
system powering problems with the A carrier (PPN or EPN).
Resolve all DC-POWER alarms. Then, repeat the test.
3. If the test continues to ABORT with a 2000 Error Code, resolve
all DUPINT (Duplication Interface) errors in a high or critical
reliability system PPN, PR-MAINT (Maintenance/Tape
Processor) errors in a standard PPN, or MAINT (EPN
Maintenance circuit pack) errors in an EPN. Repeat the test.
2029
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5
times.
Continued on next page