Maintenance Object Repair Procedures
555-233-123
10-1772
Issue 4 May 2002
1005
ABORT
(Non-TN439 circuit packs only.) This test is not valid for this
trunk translation. For this test to run, a delay dial trunk (or, for
non-TN497 circuit packs, a wink-start trunk) must be in
effect, and the trunk must be outgoing or two-way. Also, for
the TN2140 [G3iV2-386], the trunk must be
continuous-seize-ack or discontinuous-seize-ack.
1. Check trunk translation. If it is not a wink-start or delay
dial trunk, this abort message should be ignored. (For
the TN2140 [G3iV2-386], disregard this abort on a trunk
that is not continuous-seize-ack or
discontinuous-seize-ack.)
1018
ABORT
Test disabled via administration.
1. Verify that the "Maintenance Tests?" field on the Trunk
Group Form is set to "n." To enable the test, issue
change trunk-group x where "x" equals the number of
the trunk group to be tested. Then change the entry in
the "Maintenance Tests?" field on the form to "y."
1040
ABORT
(Non-TN497 circuit packs only.) This test is not performed for
trunk ports administered as access endpoints.
1. Verify this port is an access endpoint by using display
port.
2. If the port has been administered as an access endpoint,
this test should abort.
2000
ABORT
Seizure message is not received back within 10 seconds.
1. Retry the command at 1-minute intervals a maximum of
5 times.
2. If the test continues to fail, check the far-end PBX to
ensure a translation match at both ends.
3. Check the facility.
2100
ABORT
Could not allocate the necessary system resources to run
the test. This could be due to a failure to seize the port.
1. Retry the command at 1-minute intervals a maximum of
5 times.
Table 10-650.
Seizure Tests (#73, #747, #73) — Continued
Error
Code
Test
Result
Description/Recommendation
Continued on next page
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...