CARR-POW (Carrier Port Power Unit) for AC-Powered
Systems
Issue 4 May 2002
10-371
555-233-123
System Technician-Demanded Tests: Descriptions
and Error Codes
Always investigate tests in the order presented in the table below when inspecting
errors in the system. By clearing error codes associated with the Battery & Battery
Charger Query Test, for example, you may also clear errors generated from other
tests in the testing sequence.
Notes:
a. Refer to POWER (Battery & Battery Charger) Maintenance documentation
for a description of this test.
b. Refer to AC-POWER (AC Power) Maintenance documentation for a
description of this test.
c. Refer to EMG-XFER (Emergency Transfer) Maintenance documentation
for a description of this test.
d. Refer to CABINET (Cabinet Sensors) Maintenance documentation for a
description of this test.
e. Refer to EXT-DEV (External Alarm) Maintenance documentation for a
description of this test.
f. Refer to RING-GEN (Analog Ring Generator) Maintenance documentation
for a description of this test. This test only shows up in the test sequence if
there is a TN768 Tone-Clock circuit pack in the port network being tested.
Order of Investigation
Short Test
Sequence
Long Test
Sequence
D/ND
1
1
D = Destructive; ND = Nondestructive
Battery & Battery Charger Query Test (#5) (a)
X
X
ND
AC Power Query Test (#78) (b)
X
X
ND
Power Unit Query Test (carrier E) (#127)
X
X
ND
Power Unit Query Test (carrier D) (#127)
X
X
ND
Power Unit Query Test (carrier A) (#127)
X
X
ND
Power Unit Query Test (carrier B) (#127)
X
X
ND
Power Unit Query Test (carrier C) (#127)
X
X
ND
Emergency Transfer Query Test (#124) (c)
X
X
ND
Cabinet Temperature Query Test (#122) (d)
X
X
ND
External Alarm Lead Query Test (#120) (e)
X
X
ND
Analog Ring Generator Initialization Test (#117) (f)
X
X
ND
Analog Ring Generator Query Test (#118) (f)
X
X
ND
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...