ETH-PT (Control LAN Ethernet)
Issue 4 May 2002
10-751
555-233-123
1
FAIL
System software indicates at least one Ethernet link session is
down (SOME UP).
1. Isolate downed sessions (status port UUCSSpp or status
link n).
2. Follow actions based on session information.
2
FAIL
System software indicates all Ethernet sessions are down (ALL
DOWN).
1. Test the port (test port UUCSSpp) to verify the Ethernet
Local Looparound Test (#1278) result.
2. If test passes, wait for system software to indicate ALL UP.
3. If the test fails, check the destination and other components
in the path.
4. If the destination and other components in the path are
in-service, take action based on session information.
PASS
All sessions are up.
Table 10-283.
TEST #1286 Session Status Test — Continued
Error
Code
Test
Result
Description/Recommendation