UDS1-BD (UDS1 Interface Circuit Pack)
Issue 4 May 2002
10-1893
555-233-123
FAIL
Minor alarms are often accompanied by slip and misframe
alarms against the board. Trunk alarms and hardware error logs
may occur on the associated trunks.
If the UDS1 connects to a T1 network facility or to another
switch, do the following:
1. The performance of the DS1 link between the UDS1
interface circuit pack and the remote DS1 endpoint is poor.
Enter the list measurement ds1-log UUCSS command to
read the error seconds measurement.
2. Verify that both endpoints of the DS1 link are administered
using the same signaling mode, framing mode, and line
coding.
3. Contact T1 Network Service or the technician at the remote
switch to diagnose the equipment.
4. Check the physical connectivity of the UDS1 interface circuit
packs and the cable.
5. Replace the local UDS1 interface circuit pack, and repeat
the test.
FAIL
(cont’d.)
If the UDS1 connects to a line-side terminating device (for
example, a PRI terminal adapter), do the following:
1. The performance of the DS1 link between the UDS1
interface circuit pack and the line-side terminating device is
very poor. Enter the list measurement ds1-log UUCSS
command to read the error seconds measurement.
2. Verify that the switch DS1 and the line-side terminating
device are administered using the same signaling mode,
framing mode, and line coding.
3. Investigate the maintenance status of the line-side
terminating device. Obtain the error seconds measurement
on the terminating device (if possible). Refer to the
’Line-Side Terminating Device Operating Manual’ for
information.
4. Contact the vendor of the line-side terminating device to
diagnose the equipment.
5. Check the physical connection of the UDS1 interface circuit
pack to the terminating device, and check the premise
distribution system (or the intra-premise wiring) for physical
connection failures.
6. Replace the local UDS1 interface circuit pack and repeat
the test.
Table 10-678.
TEST #143 Minor Alarm Inquiry Test — Continued
Error
Code
Test
Result
Description/Recommendation
Continued on next page
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...