DIOD-DS1 (DS1 DIOD Trunk)
Issue 4 May 2002
10-595
555-233-123
2000
ABORT
Response to the test request was not received within the
allowable time period.
2100
ABORT
Could not allocate the necessary system resources to run this
test.
1. Retry the command at 1-minute intervals for a maximum of
5 times.
2053
ABORT
At least one of the following errors is found on the DS1 circuit
pack:
1281—Loss of signal
1793—Blue Alarm
2049—Red Alarm
2305—Yellow Alarm
1537—Hyperactivity
Look for the above error types in the Hardware Error Log and
follow the procedures given in the appropriate DS1-BD or
UDS1-BD maintenance documentation for the listed error
types.
FAIL
The trunk cannot be seized for an outgoing call.
1. Verify that the Trunk Type field on the trunk administration
screen form matches the trunk type administered on far
end switch.
2. Look for UDS1-BD errors in Hardware Error Log. If
present, refer to the UDS1-BD (DS1/UDS1 Trunk Circuit
Pack) Maintenance documentation.
3. Retry the test at 1-minute intervals for a maximum of 5
times.
PASS
The trunk can be seized for an outgoing call.
Table 10-221.
TEST #314 DS1 CO Dial Tone Seizure Test — Continued
Error
Code
Test
Result
Description/Recommendation
Continued on next page
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...