Power
Issue 4 May 2002
2-3
555-233-123
NOTE:
When EPN power is interrupted for greater than the cabinet holdover but
less than the control carrier holdover, calls in the control carrier are held for
the duration of the interruption but are dropped when power is restored.
Single-Carrier Cabinets
In single-carrier cabinets, there is no internal AC wiring or distribution and no
software interaction with the power system. The power supplies themselves take
about 250 milliseconds for the voltages to drop below limits.
The control cabinet that houses the Switch Processing Element (SPE) is the only
cabinet that has an internal battery reserve. All other control cabinets and port
cabinets have the 250 millisecond power supply decay delay, after which all
connections and links associated with the cabinets are dropped.
Table 2-2.
Response to Power Service Interruption with an Internal Holdover Battery
System and
Configuration
Cabinet
Holdover for
Entire Cabinet
(in seconds)
Holdover for Entire
Control Carrier (in
minutes)
Standard
PPNMCC
10
10
High, Critical
PPNMCC
10
5
Standard/High, Critical
PPN SCC/ESCC
1/4
2
Standard/High, Critical
1
1
The holdover times listed are in effect if the EPN contains a TN775 maintenance circuit pack.
However, if the EPN contains a TN775B maintenance circuit pack, the holdover time for the entire
cabinet is 10 seconds, and the holdover time for the control carrier is 10 minutes.
EPN MCC
15
none
Standard/High, Critical
EPN SCC/ESCC
1/4
none
Table 2-3.
Types of Cabinet Power Interruption
System and
Cabinet
Shorter Holdover
Than Entire
Cabinet
Longer Holdover than
Entire Cabinet, Shorter
Holdover than Control
Carrier
Longer Holdover
Than Control
Carrier
PPN SCC
No calls dropped
All calls dropped
System reloads
EPN SCC
No calls dropped
All calls dropped
System reloads
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...