Flash Data Consistency Check Test (#421)
The software vintage number, translation time stamps, announcement time
stamps, and update file time stamps and identifiers are read off of both memory
cards or SPEs and then compared. If the comparison shows any discrepancy,
FL-DATA is alarmed. This test is only run in a High or Critical Reliability system.
The test is run as part of the test card-mem long and as part of the standby PE
scheduled maintenance.
Table 10-303.
TEST #421 Flash Data Consistency Check Test
Error Code
Test
Result
Description/Recommendation
0
ABORT
The test timed out without completing. This error can occur
when the system is heavily loaded and the test is not
allocated sufficient time to run.
1. Rerun the test when the system is less busy and is not
running standby maintenance.
1029 1030
2011 2012
2013 2014
2015 2016
2017 2018
2019 2020
2021 2022
2023 2024
2025 2051
ABORT
Refer to the STBY-SPE (Standby SPE) Maintenance
documentation for a description of these error codes.
9005
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum
of 5 times.
35498
ABORT
Difficulty was encountered trying to send information
between the SPEs.
35512
ABORT
The Standby SPE cannot be put into maintenance mode.
1. Check for and resolve all DUPINT (Duplication
Interface Circuit Pack), SHDW-LNK (Memory
Shadowing Link), SHDW-CIR (Common Shadow
Circuit), and STBY-SPE (Standby SPE) alarms.
2. Retry the command.
35514
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum
of 5 times.
Continued on next page
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...