Troubleshooting power units
Issue 4 May 2002
5-17
555-233-123
1. Remove the four screws on the top of the cabinet.
2. Remove the four screws from the fan panel at the rear of the unit.
3. Remove the fan panel.
4. If the unit is attached to the wall, disconnect the entire fan panel.
5. A cable assembly extends from the power supply and plugs into the
backplane with a Burndy connector. Squeeze the sides of the connector to
release the latch. Then pull the connector off of the backplane. See
.
Figure 5-4.
Power supply sub-assembly (inside view)
6. Remove the power supply from the unit. Once the power supply is
removed, disconnect the AC power cord.
7. Reconnect the AC power cord, insert the new power supply, reconnect the
Burndy connector and the cord, reinsert (if removed) the reconnected fan
panel, screw the fan panel back onto the unit, and reinsert the screws on
the top of the unit.
To Backplane
P/O
(Plug to
Power Supply)
Circuit
Breaker
Wire
Assembly
(Green)
P/O
(Blue)
P/O
(Brown)
Wire
Assembly
(Blue)
Wire
Assembly
(Brown)
Circuit Module
(Green-Yellow
Wire Attaches to
Ground Block Screw)
P/O, PI Cable,
TY Wrap
Screw
Screw
Summary of Contents for Definity SI
Page 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Page 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Page 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Page 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Page 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Page 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...