CABINET (Cabinet Sensors)
Issue 5 October 2002
851
555-233-119
1
FAIL
(cont’d.)
There is a problem with the environment of the power system:
7. The power unit could be defective. Refer to the
‘‘Removing Power’’
and
‘‘Restoring Power’’
sections in
Chapter 1, ‘‘Maintenance for CSI
systems’’
.
a. If the yellow LED is off, replace the power unit.
b. If the Active Tone-Clock circuit pack loses power, the system
performs a Cold-2 restart to finish (the login prompt appears at the
administration terminal).
c. Rerun the test.
PASS
There is neither a power nor fan a problem in any of the cabinets. If a
problem is reported, troubleshoot by using the procedures for the FAIL
cases described previously.
Table 131.
TEST #122 Cabinet Temperature Query Test
—
Continued
Error
Code
Test
Result
Description/ Recommendation
Continued on next page
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...