MAPD-BD (MAPD Interface Circuit Pack TN802)
Issue 5 October 2002
1359
555-233-119
If the circuit pack has an entry in the circuit plan and either of the other two
conditions are not met, a MINOR alarm is logged. To resolve the error,
either:
1. Make sure the circuit pack is properly administered and that a
functioning MAPD circuit pack is inserted in the correct slot, OR
2. Completely remove the MAPD-BD from the system:
a. Shut down NT (see
‘‘Shutting down NT on the TN802’’
)
b. Remove any administered DS1 trunks, access endpoints, or
PRI endpoints associated with the circuit pack from their
respective trunk groups.
c. Remove the DS1 (remove ds1 UUCSS) and circuit pack
(change circuit pack UUCSS) administration.
If the circuit pack is properly administered and the red LED is still on, follow
the instructions for LED Alarms with Error Type 1 in Chapter 7.
b. Error Type 2: NT is down and the system attempts to reset the board. If the
reset fails, the board is probably bad.
1. Replace the circuit pack.
c. Error Type 18: the circuit pack has been busied out.
1. Release the board (release board UUCSS).
d. Error Type 23 and 1025: the MAPD-BD circuit pack is not completely
administered. In addition to insertion, the MAPD circuit pack must have all
of the following administration:
■
Have an entry in the circuit plan (change circuit pack)
■
Be administered as DS1 (add ds1 UUCSS)
The MAPD circuit pack differs from others in that inserting it into the switch
backplane is not enough to make the board usable.
e. Error Type 125, no Aux Data: A wrong circuit pack is inserted in the slot
where this circuit pack is logically administered. To resolve this problem,
either:
1. Remove the wrong circuit pack and insert the logically administered
circuit pack, OR
2. Re-administer this slot (change circuit-pack) to match the circuit
pack inserted.
f. Error Type 257: this error is associated with the Common Port Circuit Pack
Maintenance Test. Refer to XXX-BD (Common Port Circuit Pack)
Maintenance documentation for details.
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...