RING-GEN (Analog Ring Generator)
Issue 5 October 2002
1573
555-233-119
Table 445.
TEST #118 Analog Ring Generator Query Test
Error
Code
Test
Result
Description/ Recommendation
1
1000
1001
1003
1115
2012
2100
ABORT
Could not seize the resources to run the test. Other maintenance is running
on the active tone/clock circuit pack.
1. Wait for the green LED on the active tone/clock circuit pack to go out;
(use the status port-network command to determine the Active
tone/clock circuit pack).
2. Rerun the test. If the test aborts again, refer to TDM-CLK (TDM Bus
Clock) Maintenance documentation.
2000
ABORT
Response to the request was not received within the allowable time period.
1. Look for TDM-CLK errors and alarms. Resolve all other tone/clock
problems first.
2. Rerun the test.
1005
ABORT
The tone/clock is unable to read the analog ringing voltage level when the
tone/clock is in the Processor Interface slot. This test is not available for the
Processor Port Network in this configuration.
FAIL
This failure indicates that there is no ringing voltage in the carrier where the
active tone/clock circuit pack resides. Other carriers may or may not have
ringing voltage.
1. Unseat all analog circuit packs in the cabinet that contains the
Tone/Clock circuit pack and rerun the test.
2. If the test passes, then the Ring Generator is healthy and one of the
analog circuit packs is defective. Replace the analog circuit packs one
at a time, and rerun the test to determine which circuit pack is causing
the problem. When the defective analog circuit pack is found, replace it.
Rerun the test. If the test still fails, go to Step 4.
3. Replace the 650A power unit, and rerun the test. If the test still fails, go
to Step 4.
4. The tone/clock may be faulty and incorrectly reporting the level of the
ringing voltage. Replace the tone/clock and rerun the test. Refer to
‘‘TONE-BD (Tone-Clock Circuit Pack)’’
Maintenance documentation for
details on replacing the tone/clock circuit pack. Rerun the test.
PASS
Ringing voltage is acceptable in the cabinet containing the tone/clock circuit
pack.
Continued on next page
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...