UDS1-BD (UDS1 Interface Circuit Pack)
Issue 5 October 2002
1769
555-233-119
If the circuit pack has an entry in the circuit plan and either of the other two
conditions are not met, a MINOR alarm is logged. To resolve the error
either:
1. Make sure that all conditions for administration are met and that a
functioning UDS1 circuit pack is inserted in the correct slot, or
2. Completely remove the UDS1-BD from the system using the
following steps:
a. Remove any administered DS1 trunks, access endpoints or
PRI endpoints associated with the circuit pack from their
trunk groups.
b. Execute the remove ds1 UUCSS and change circuit pack
UUCSS commands.
If all the administration conditions are met for this circuit pack and the red
LED is still on, follow the instructions for LED Alarms with Error Type 1 in
Chapter 7.
b. Error Type 18 — The UDS1 Interface circuit pack has been busied out by
a busyout board UUCSS command.
c. Error Type 23 — The UDS1-BD circuit pack is not completely
administered. To be fully administered, the UDS1 circuit pack must:
1. Have an entry in the circuit plan using the change circuit pack
command,
2. Be administered using the add ds1 UUCSS command, and
3. Be physically inserted into the correct slot.
A DS1 (UDS1-BD and DS1-BD) differs from most circuit packs in that
inserting the circuit pack into the switch is not enough to make the board
usable. It must also be administered with the add ds1 command.
d. Error Type 125: No Aux Data — An incorrect circuit pack is inserted in the
slot where the USD1 circuit pack is logically administered. To resolve this
problem, either remove the incorrect circuit pack and insert the logically
administered circuit pack, OR use the change circuit-pack command to
re-administer this slot to match the circuit pack inserted.
Aux Data 3 — The 24/32-channel option jumper setting on the circuit pack
does not match the option set on the DS1 Circuit Pack administration
form. The circuit pack must be physically removed to see the setting of the
jumper.
e. Error Type 257 — is associated with the Common Port Circuit Pack
Maintenance Test. Refer to XXX-BD (Common Port Circuit Pack)
Maintenance documentation for details.
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...