CABINET (Cabinet Sensors)
Issue 5 October 2002
849
555-233-119
Cabinet Temperature Query Test (#122)
This test queries the Processor circuit pack for the status of the cabinet sensors in
the Compact Modular Cabinet. The 650A Power Supply is equipped with thermal
protection that shuts the power supply down if the internal temperature exceeds
the maximum rated safe operating temperature. Only one alarm lead is supported
by this cabinet type to indicate both a power or a fan problem.
This means that a failure of this test can also mean a power problem, not
necessarily just a temperature (fan) problem. Also, alarm leads from multiple
cabinets are tied into one single lead.
Table 131.
TEST #122 Cabinet Temperature Query Test
Error
Code
Test
Result
Description/ Recommendation
1000
ABORT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2000
ABORT
Response to the test request was not received within the allowable time
period.
2029
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1
FAIL
There is a fan and/or power problem in one or more of the cabinets. The
LEDs on the power supply may indicate the problem source. Otherwise
follow the procedures below for each cabinet:
1. If none of the fans are running:
a. Verify 8-14 volt DC power is available to the fan units by checking
the wiring connector.
— If there is 8-14 volt DC power at the connector, there should be
power to the fans. If the fans still do not run, replace the fan
assembly.
— If there is no 8-14 volt DC power at the connector, the power unit
fan output is defective or thermally shut down. Let the power unit
cool and recycle AC input power. If not fan output, replace the
power unit. If the fans still do not run, escalate the problem.
2. If only 1 of the fans is not running, replace the fan.
3. If all the fans can be started, wait five minutes and rerun the test. If the
test fails again, go to Step 4 or 5 as applicable.
Continued on next page
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...