TIME-DAY (Time of Day)
Issue 5 October 2002
1717
555-233-119
To resolve the alarm, do the following:
1. Use the set time command to set the time of day.
2. Use the display time command to display the time of day. If the time of day
is displayed correctly, wait 15 minutes and verify that the alarm is retired. If
the alarm has not been retired, continue with Step 3.
3. Test the active TN1648 SYSAM circuit pack using the test maintenance [a
| b] sh command. If any tests fail, refer to the repair procedures for the
SYSAM circuit pack before further investigating time-of-day problems. If all
tests PASS and the alarm has not been retired, proceed to Step 4.
4. Replace the active TN1648 SYSAM circuit pack must be replaced. See
“Replacing SPE Circuit Packs” in Chapter 5. The alarm should be resolved
within 15 minutes of replacing the SYSAM and resetting the time with set
time.
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...