DID-TRK (DID Trunk)
Issue 5 October 2002
1005
555-233-119
1004
ABORT
The port was seized by a valid call during the test. The test has been
aborted. Use the display port PCSSpp command to determine the station
extension, attendant number, or trunk group/member number of the port.
Use the status station, status attendant, or status trunk command to
determine the service state of the port. If the service state indicates that the
port is in use, then the port is unavailable for certain tests. You must wait
until the port is idle before retesting. Attendants are always in use (off-hook)
if the handset is plugged in and the port is not busied out.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2000
ABORT
Response to the test request was not received within the allowable time
period.
2100
ABORT
Could not allocate the necessary system resources to run this test. This
could be due to a failure to seize the port.
1. Retry the command at 1-minute intervals a maximum of 5 times.
Any
FAIL
This test can fail due to on-board or off-board problems. Off-board
problems of concern include EXP-INTF faults, TDM-BUS faults, and faults
associated with the tone detectors/tone generators. Clear all off-board
problems before replacing the board. Keep in mind that a TDM-BUS
problem is usually the result of a faulty board connected to the backplane or
bent pins on the backplane.
1. Look for EXP-INTF errors in the error log. If present, refer to the
EXP-INTF Maintenance documentation.
2. Look for TDM-BUS errors in the error log. If present, refer to the
TDM-BUS Maintenance documentation.
3. Look for TONE-BD and/or TONE-PT errors in the error log. If present,
refer to the TONE-BD Maintenance documentation and the TONE-PT
Maintenance documentation.
4. Test the board when the faults from steps 1, 2, and 3 are cleared.
Replace the board only if the test fails.
PASS
The port is correctly using its allocated time slots. User-reported troubles on
this port should be investigated using other port tests and by examining
station, trunk, or external wiring.
Table 189.
TEST #6 NPE Crosstalk Test — Continued
Error
Code
Test
Result
Description/ Recommendation
Continued on next page
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...