Maintenance Objects
1770
Issue 5 October 2002
f. Error Type 513 — The UDS1 Interface circuit pack has detected a
transient hardware problem. The value in the Aux Data field indicates the
type of hardware problem:
If the UDS1 board detects only one of these hardware problems, then the
error will disappear when none of these faults are detected for 10 minutes.
If the same Aux Data value is logged more than once in a 24 hour period,
the circuit pack should be replaced.
g. Error Type 514 — LAN External RAM Error. This error occurs when there
is a hardware fault in the PPE external RAM. The RAM is used for
message buffering to and from the Packet Bus. This error should not occur
frequently. If it does (10 times within 30 minutes), the circuit pack should be
replaced.
h. Error Type 769 —Transmit FIFO Underflow Error. This error occurs when
the circuit pack cannot find the “end of frame” bit when transmitting a frame
to the Packet Bus. An alarm is raised if this error occurs three times within
10 minutes. Clear the alarm using the following commands: busyout
board UUCSS, reset board UUCSS, test board UUCSS long, release
board UUCSS. If the error recurs within 10 minutes, replace the circuit
pack.
i. Error Type 770 — Unable to Write LAN Translation RAM Error. This error
occurs when a call is aborted because there are no available translation
RAM locations for the call connection attempt. An alarm is raised if this
error occurs two times within 10 minutes. Clear the alarm using the
following commands: busyout board UUCSS, reset board UUCSS, test
board UUCSS long, release board UUCSS. If the error recurs within 10
minutes, replace the circuit pack.
j. Error Type 1300 — CSU Module/T1 Sync Splitter missing or E1
Synchronization Splitter (E1SS) missing.
CSU Module/T1 Sync Splitter missing: The
Near-End CSU Type
field
on the add ds1 form has been administered as
integrated
but the
120A1 CSU Module or the 401A T1 Sync Splitter is not physically
connected (or is improperly connected) to the UDS1 board on the back of
the port carrier.
If using the 120A1 CSU Module or the 401A T1 Sync Splitter, plug (or
replug) the CSU Module/T1 Sync Splitter into the UDS1 circuit pack’s
connector on the I/O connector panel on back of the carrier. Otherwise,
change the
Near-End CSU Type
field using the change ds1 form to
other
.
Aux Data
Problem
4352
External RAM failure
4353
Internal RAM failure
4355
Internal ROM failure
Содержание DEFINITY Server CSI
Страница 1: ...Maintenance for Avaya DEFINITY Server CSI Volumes 1 and 2 Release 1 2 555 233 119 Issue 5 October 2002...
Страница 6: ......
Страница 20: ...Contents 555 233 119 20 Issue 5 October 2002...
Страница 30: ...About this Book 555 233 119 30 Issue 5 October 2002...
Страница 944: ...Maintenance Objects 555 233 119 944 Issue 5 October 2002...
Страница 1397: ...MMI BD Issue 5 October 2002 1397 555 233 119 Figure 44 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1409: ...MMI PT Issue 5 October 2002 1409 555 233 119 Figure 45 TN787 Multimedia Interface MMI Circuit Pack...
Страница 1891: ...VC DSPPT Issue 5 October 2002 1891 555 233 119 Figure 63 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 1902: ...Maintenance Objects 1902 Issue 5 October 2002 Figure 65 VC Circuit Pack Summer Port Loopback Test...