Parameters
List of parameters
1-990
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source (BO/CO parameter, BICO coded) to search in the signal drains.
The question is answered:
How often is a connection made to a signal source in the drive object and from which index are these interconnec-
tions saved (r9482[0...59], r9483[0...59])?
Dependency:
Refer to: r9481, r9482, r9483, r9485, r9486
Description:
Displays the number of BICO interconnections to the signal drain being searched for.
The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482[0...59] and r9483[0...59] and is specified by the count (r9485) and the first
index (r9486).
Dependency:
Refer to: r9481, r9482, r9483, p9484, r9486
Description:
Displays the first index of the signal source being searched for.
The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482[0...59] and r9483[0...59] and is specified by the count (r9485) and the first
index (r9486).
Dependency:
Refer to: r9481, r9482, r9483, p9484, r9485
p9484
BICO interconnections search signal source / BICO S_src srch
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, SERVO,
S_INF, TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41,
TM54F_MA,
TM54F_SL, VEC-
TOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
0
Min Max
Factory
setting
0 4294967295
0
r9485
BICO interconnections signal source search count / BICO S_src srchQty
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, SERVO,
S_INF, TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41,
TM54F_MA,
TM54F_SL, VEC-
TOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
0
Min Max
Factory
setting
- -
-
r9486
BICO interconnections signal source search first index / BICO S_src srchIdx
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, SERVO,
S_INF, TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41,
TM54F_MA,
TM54F_SL, VEC-
TOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
0
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...