Parameters
List of parameters
1-724
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
When the 690 V input is used (X522) without voltage scaler,, 0 % should be entered.
When the 100 V input (X521) is used with voltage scaler to measure medium voltages, the dividing (scaling) factor
multiplied by 100% should be entered.
Example:
1000 V line supply voltage, voltage scaling, 10:1
--> voltage at the VSM input is 100 V
--> p3660 = 10 * 100 % = 1000 %
Description:
Sets the voltage scaler for the Voltage Sensing Module (VSM).
Note:
When the 690 V input is used (X522) without voltage scaler,, 0 % should be entered.
When the 100 V input (X521) is used with voltage scaler to measure medium voltages, the dividing (scaling) factor
multiplied by 100% should be entered.
Example:
1000 V line supply voltage, voltage scaling, 10:1
--> voltage at the VSM input is 100 V
--> p3660 = 10 * 100 % = 1000 %
Description:
Displays the voltage between L1 and L2.
Dependency:
Refer to: r0025, r0072, p3660
Note:
X521.1 or X522.1: Connection of L1
X521.2 or X522.2: Connection of L2
X521.3 or X522.3: Connection of L3
The absolute voltage value (3-ph. AC) resulting from the phase voltages is displayed unsmoothed in r0072[1] and
smoothed in r0025[1].
Description:
Displays the voltage between L1 and L2.
Dependency:
Refer to: p3660
Note:
X521.1 or X522.1: Connection of L1
X521.2 or X522.2: Connection of L2
X521.3 or X522.3: Connection of L3
p3660[0...n]
VSM input line supply voltage, voltage scaler / VSM inp V_scaler
VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
p0150
Func. diagram:
9880
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
100000.00 [%]
0.00 [%]
r3661
CO: VSM input line supply voltage u1 - u2 / VSM inp u1-u2
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8850, 8950,
9880
P-Group:
Closed-loop control
Units group:
5_3
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [V]
- [V]
- [V]
r3661[0...n]
CO: VSM input line supply voltage u1 - u2 / VSM inp u1-u2
VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
p0150
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
5_3
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [V]
- [V]
- [V]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...