![Siemens SINAMICS S Series Скачать руководство пользователя страница 85](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427085.webp)
List of parameters
Parameters
1-85
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Setting to activate/de-activate a drive object.
Values:
0:
De-activate drive object
1:
Activate drive object
2:
Drive object, de-activate and not present
Recommend.:
After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
Dependency:
Refer to: r0106
Refer to: A01316
Caution:
It is not permissible to de-activate drive objects with safety functions enabled.
Notice:
The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be canceled.
Note:
Setting a drive object to de-activate principally corresponds to the "parking axis" function. however, here, all of the
DRIVE-CLiQ components, assigned to the drive object, are in involved.
Description:
Displays the "active/inactive" state of a drive object.
Values:
0:
Drive object inactive
1:
Drive object active
Dependency:
Refer to: p0105
Description:
The type of an existing drive object is entered into each index.
Values:
0:
-
1:
SINAMICS S
2:
SINAMICS G
3:
SINAMICS I
4:
SINAMICS CX32
5:
SINAMICS GM
7:
SINAMICS GL
p0105
Activate/de-activate drive object / DO act/de-act
A_INF, B_INF,
CU_LINK, DMC20,
SERVO, S_INF,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41, VEC-
TOR
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 2
1
r0106
Drive object active/inactive / DO act/inact
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, DMC20,
SERVO, S_INF,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41, VEC-
TOR
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
-
p0107[0...15]
Drive object type / DO type
CU_CX32, CU_S
Can be changed:
C1(2)
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 254
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...