Parameters
List of parameters
1-118
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the inductance between the filter and power unit.
Note:
The parameter is automatically pre-assigned depending on the power unit being used and matches the specified
Siemens commutating reactors.
For a parallel circuit, the value corresponds to the inductance of a power unit.
Description:
Sets the resistance between the filter and power unit
Note:
The parameter is automatically pre-assigned depending on the power unit being used and matches the specified
Siemens commutating reactors.
For a parallel circuit, the value corresponds to the resistance of a power unit.
Description:
Sets the inductance between line supply and filter.
Note:
The value must be, for example, appropriately increased if an additional inductance (reactor or transformer is
installed in front of the filter).
Description:
Sets the resistance between the line supply and filter.
Note:
The value must be, for example, appropriately increased if an additional resistor is installed in front of the filter.
p0223
Infeed inductance between filter and power unit / INF L filter/PU
A_INF, S_INF
Can be changed:
C2(1)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8850, 8950
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.001 [mH]
1000.000 [mH]
2.100 [mH]
p0224
Infeed resistance between filter and power unit / INF R filter/PU
A_INF, S_INF
Can be changed:
C2(1)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8850, 8950
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00000 [Ohm]
100.00000 [Ohm]
0.00100 [Ohm]
p0225
Infeed inductance between line supply and filter / INF L line/filter
A_INF, S_INF
Can be changed:
C2(1)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8850, 8950
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.001 [mH]
1000.000 [mH]
0.001 [mH]
p0226
Infeed resistance between line supply and filter / INF R line/filter
A_INF, S_INF
Can be changed:
C2(1)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8850, 8950
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Ohm]
100.00 [Ohm]
0.00 [Ohm]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...