Parameters
List of parameters
1-366
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Description:
Sets the dynamic factor for the Vdc-min controller (kinetic buffering).
100 % means that p1290, p1291 and p1292 (gain, integral time and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, then this can be realized using the dynamic factor. In this case p1290,
p1291, p1292 are weighted with the dynamic factor p1287.
If several modules are connected to the DC link, then the dynamic factor must be increased corresponding to the
ratio of the additional capacitances to the capacitance of the module involved.
Note:
The pre-setting of the dynamic factor is based on the power units connected at DRIVE-CLiQ. It is assumed that the
power unit, connected via DRIVE-CLiQ is also electrically connected to the DC link. If this is not the case, then the
dynamic factor must be optimized manually.
Description:
Sets the lower speed threshold for the Vdc_max controller. When this speed threshold is fallen below, the Vdc_max
control is switched-out and the speed is controlled using the ramp-function generator.
Description:
Sets the proportional gain for the Vdc controller (DC link voltage controller).
Note:
The gain factor is proportional to the capacitance of the DC link. The parameter is preset to a value that is optimally
adapted to the capacitance of the individual Motor Module. The capacitances of the other power units, which are
connected to the DC link, can be taken into account using the dynamic factor (p1287 or p1283).
r1286
Vdc_min controller switch-in level (kinetic buffering) (V/f) / Vdc_min on_level
VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6320
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [V]
- [V]
- [V]
p1287[0...n]
Vdc_min controller dynamic factor (kinetic buffering) (V/f) / Vdc_min dyn_factor
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 [%]
10000 [%]
100 [%]
p1289[0...n]
Vdc_max controller speed threshold (V/f) / Vdc_max n_thresh
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Functions
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [RPM]
210000.0 [RPM]
10.0 [RPM]
p1290[0...n]
Vdc controller proportional gain (V/f) / Vdc_ctrl Kp
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6320
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 100.00
1.00
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...