List of parameters
Parameters
1-341
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
Re bit 00:
Status to display the single initialization after POWER ON.
Re bit 01:
State in which the automatic restart function waits for faults (initial state).
Re bit 02:
General display that a fault has been identified and that the restart or acknowledgement has been initiated.
Re bit 03:
Displays the acknowledge command within the "acknowledge alarms" status (bit 4 = 1). For bit 5 = bit 6 = 1, the
acknowledge command is continually displayed.
Re bit 04:
State in which the faults that are present are acknowledged. The status is exited again after successful acknowl-
edgement. A change is only made into the next state if it is signaled that a fault is no longer present after an
acknowledgement command (bit 3 = 1).
Re bit 05:
State in which the drive is automatically powered-up (only for p1210 = 4, 6).
Re bit 06:
State in which the system waits after having been powered-up, to the end of the start attempt.
For p1210 = 1, this signal is directly set after the faults have been successfully acknowledged.
Re bit 07:
State, which is assumed after a fault occurs within the automatic restart function.
Re bits 12 ... 15:
Actual state of the start counter (binary coded).
Description:
Automatic restart (AR) status word.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization
Yes
No
-
01
Wait for alarm
Yes
No
-
02
Auto restart active
Yes
No
-
03
Setting the acknowledgement command
Yes
No
-
04
Acknowledge alarms
Yes
No
-
05
Restart
Yes
No
-
06
Delay time running after automatic power-
up
Yes
No
-
07
Fault
Yes
No
-
12
Start count. bit 0
On
Off
-
13
Start count. bit 1
On
Off
-
14
Start count. bit 2
On
Off
-
15
Start count. bit 3
On
Off
-
r1214.0...15
CO/BO: Automatic restart, status / AR status
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization
Yes
No
-
01
Wait for alarm
Yes
No
-
02
Auto restart active
Yes
No
-
03
Setting the acknowledgement command
Yes
No
-
04
Acknowledge alarms
Yes
No
-
05
Restart
Yes
No
-
06
Delay time running after automatic power-
up
Yes
No
-
07
Fault
Yes
No
-
12
Start count. bit 0
On
Off
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...