Description:
Displays the status of the DC link voltage monitoring for the master/slave.
Dependency:
Refer to: r0088, p3510, p3574
Description:
Displays the status of the closed-loop infeed control.
Values:
0:
Initialization running
1:
Pulse enable missing
2:
Ramp-up, DC-link voltage
3:
Ramp-up reactive current
4:
Shutdown running
5:
Reset identification
6:
Operation
7:
Identification running
8:
Smart mode running
Description:
The D component of the current pre-control is determined from the device data of the filter. p3603 can be used to
weigh the pre-calculated D component. If no dynamic pre-control is to be used, set the factor to zero.
Description:
Displays the system deviation of the active current controller.
r3575.0...2
BO: Master/slave DC link voltage monitoring status / Vdc monit status
A_INF (Mas-
ter/Slave)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
8948
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Upper limit value reached
Yes
No
-
01
Lower limit value reached
Yes
No
-
02
Upper/lower limit value reached
Yes
No
-
r3602
Infeed control status / INF ctrl state
A_INF
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0000 bin
1000 bin
-
p3603
Infeed current pre-control factor D component / INF I_ctrl D-comp
A_INF
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8946
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
500.00 [%]
100.00 [%]
r3606
Infeed active current controller system deviation / INF I_act ctrl dev
A_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8946
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...