Description:
Sets the de-magnetizing time (for induction motors) after the inverter pulses have been canceled.
The inverter pulses cannot be switched-in (enabled) within this delay time.
Note:
The parameter is calculated using p0340 = 1, 3.
For induction motors, the result depends on the rotor time constant (r0384).
if this time is shortened too much, then this can result in an inadequate de-magnetization of the induction motor and
in an overcurrent condition when the pulses are subsequently enabled (only when the flying restart function is acti-
vated and the motor is rotating).
Description:
Sets the speed at the start of field weakening for a DC link voltage of 600 V.
Dependency:
Refer to: p0320, r0331
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the velocity at the start of field weakening for a DC link voltage of 600 V.
Dependency:
Refer to: p0320, r0331
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the actual system of units for motor equivalent circuit diagram data.
p0347[0...n]
Motor de-excitation time / Mot t_de-excitat.
VECTOR
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
20.000 [s]
0.000 [s]
p0348[0...n]
Speed at the start of field weakening Vdc = 600 V / Mot n_field weaken
SERVO
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
5722
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [RPM]
210000.0 [RPM]
0.0 [RPM]
p0348[0...n]
Velocity at the start of field weakening Vdc = 600 V / Mot v_field weaken
SERVO (Lin)
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
5722
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [m/min]
1000.0 [m/min]
0.0 [m/min]
p0349
System of units, motor equivalent circuit diagram data / Unit_sys mot ESB
SERVO, VECTOR
Can be changed:
C2(3)
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 2
1
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...