List of parameters
Parameters
1-703
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Index:
[0] = Run 1
[1] = Run 2
Dependency:
Refer to: p3410
Note:
The value measured in the first identification run (for p3410 = 1, 3, 4, 5) is displayed in r3412[0]. For p3410 = 1, 3,
this value is transferred to p3422.
The DC link capacitance is not measured at the second identification run.
The total DC link capacitance of a DC link group comprises the sum of the sub-capacitances of all motor/infeed
modules and the additional DC link capacitors.
Description:
Displays the identified line supply inductance.
The value corresponds to the total inductance between the stiff line supply and the connection point of the Voltage
Sensing Module (VSM).
Index:
[0] = Run 1
[1] = Run 2
Dependency:
Refer to: p3410
Notice:
The value is only automatically determined for the line supply identification (p3410 > 0), if operation with a Voltage
Sensing Module is selected (p3400.5 = 1). Otherwise, r3414 = 0 is displayed.
Note:
The value measured in the first identification run is displayed in r3414[0] (for p3410 = 1, 3, 4, 5). This value is trans-
ferred to p3421.
The value measured in the second identification run is displayed in r3414[1] (for p3410 = 4, 5).
For the inductance value of the commutating reactor, r3411 - r3414 applies.
Description:
Sets the magnitude of the excitation frequency for the L identification.
The setting is made as a percentage of the maximum power unit current (r0209).
Index:
[0] = Run 1
[1] = Run 2
Dependency:
Refer to: p3410, r3411, p3421, p3620, p3622
Notice:
To correctly identify the current level (p3410 = 4, 5) depending on the reactor inductance, the following must apply:
p3415[0] < p3415[1]
For A_INF booksize units, the following applies:
The interrelationship between the reactor inductance and the current magnitude should be measured. Generally,
the factory setting of p3415[0] and p3415[1] should be kept.
For chassis units and S_INF booksize units, the following applies:
Generally, there is only a very low inter-relationship between the reactor inductance and the current magnitude.
This means that for the factory setting p3415[0] = p3415[1] = 20 %, i.e. run 2 is not executed.
Note:
The reactive current for identification run 1 is set in p3415[0] (basic controller setting).
The reactive current for identification run 2 is set in p3415[1] (adaptation of the current controller when reducing the
reactor inductance with increasing current magnitude).
r3414[0...1]
Infeed, line supply inductance identified / INF t_line ident
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [mH]
- [mH]
- [mH]
p3415[0...1]
Infeed excitation current L identification / INF I_exc L_Ident
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1.00 [%]
75.00 [%]
20.00 [%]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...