Parameters
List of parameters
1-1008
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the tolerance for the cross-check of the actual position between the two monitoring channels.
Dependency:
Refer to: C01711
Note:
A change only becomes effective after a POWER ON.
Description:
Sets the tolerance for the cross-check of the actual position between the two monitoring channels.
Dependency:
Refer to: C01711
Note:
A change only becomes effective after a POWER ON.
Description:
Sets the tolerance to check the actual values after referencing (incremental encoder) or when powering-up (abso-
lute encoder).
Dependency:
Refer to: C01711
Note:
A change only becomes effective after a POWER ON.
Description:
Sets the tolerance to check the actual values after referencing (incremental encoder) or when powering-up (abso-
lute encoder).
Dependency:
Refer to: C01711
Note:
A change only becomes effective after a POWER ON.
p9542
SI motion act val comparison tol (crosswise) (Control Unit) / SI Mtn act val tol
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0010 [mm]
360.0000 [mm]
0.1000 [mm]
p9542
SI motion act val comparison tol (crosswise) (Control Unit) / SI Mtn act val tol
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0010 [°]
360.0000 [°]
0.1000 [°]
p9544
SI motion actual value comparison tolerance (referencing) (CU) / SI Mtn ref tol
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0000 [mm]
36.0000 [mm]
0.0100 [mm]
p9544
SI motion actual value comparison tolerance (referencing) (CU) / SI Mtn ref tol
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0000 [°]
36.0000 [°]
0.0100 [°]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...