Faults and Alarms
List of faults and alarms
3-1498
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F01913 (N, A)
COMM INT: Monitoring time sign-of-life expired
Drive object:
All objects
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: OFF1 (NONE, OFF2, OFF3)
VECTOR: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection between the drive and the higher-level control (SIMOTION, SINUMERIK) has been interrupted for
the following reasons:
- the control was reset.
- the data transfer to the control was interrupted.
Remedy:
- wait until the control has re-booted.
- restore data transfer to the control.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01914 (N, A)
COMM INT: Monitoring time configuration expired
Drive object:
All objects
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: OFF1 (NONE, OFF2, OFF3)
VECTOR: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the configuration has expired.
Fault value (r0949, interpret decimal):
0: The transfer of the send-configuration data has been exceeded (time).
1: The transfer of the receive-configuration data has been exceeded (time).
Remedy:
- acknowledge faults that are present.
- carry out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A01915
IF1: PB/PN clock cycle synchronous operation sign-of-life failure drive object 1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Group display for problems with the sign-of-life of the master (PROFIBUS clock-cycle synchronous [isochronous])
on the Drive Object 1 (Control Unit).
For central measurements, synchronism with the master is lost.
Remedy:
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
A01920 (F)
PROFIBUS: Interruption cyclic connection
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic connection to the PROFIBUS master is interrupted.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...