List of parameters
Parameters
1-701
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
Re bit 02:
When phase failure is detected the bit is set and alarm A06205 is output.
The bit is reset for the following events:
- the infeed had reached the normal operating state again after a phase failure has been bypassed/buffered (p3402
= 9).
- the pulse enable is withdrawn due to a fault or powering-down with OFF1/OFF2.
Description:
Displays the status word of the infeed.
Description:
Sets the mode to detect the line supply frequency.
Values:
0:
Line supply frequency setting 50/60 Hz off
1:
Line supply frequency setting 50/60 Hz on
Dependency:
Refer to: p0211, p0284, p0285
Refer to: A06350, A06351, F06500
Note:
For p3409 = 1, the following applies:
After operation has been enabled, the rated line supply frequency (p0211) is automatically set to a value of 50 Hz or
60 Hz corresponding to the currently measured frequency. This means that the parameter value of p0211 is, under
certain circumstances, changed.
For p3409 = 0, the following applies:
The system does not change parameter p0211.
Description:
Sets the line and DC link parameter identification routine for the infeed module.
Values:
0:
Identification (Id) off
1:
Activate identification (Id)
2:
Set controller settings
3:
Save identification and controller settings
4:
Save identification and controller settings with L adaptation
5:
Reset, save Id and controller setting with L adaptation
r3405.7
CO/BO: Status word infeed / INF ZSW
B_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
07
DC link undervoltage alarm threshold fallen
below
Yes
No
-
p3409
Infeed line frequency setting / INF f_line_mode
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
1
p3410
Infeed identification method / INF Ident_type
A_INF, S_INF
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 5
5
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...