List of parameters
Parameters
1-575
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Number of alarms that have occurred after the last reset.
Dependency:
When p2111 is set to 0, the following is initiated:
- all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63].
- the alarm buffer [0...7] is deleted.
Refer to: r2110, r2122, r2123, r2124, r2125
Note:
The parameter is reset to 0 at POWER ON.
Description:
Sets the signal source for external alarm 1.
Dependency:
Refer to: A07850
Note:
An external alarm is triggered with a 1/0 signal.
Description:
Sets the signal source for external alarm 1.
Dependency:
Refer to: A07850
Note:
An external alarm is triggered with a 1/0 signal.
Description:
Displays the total system runtime for the drive unit.
The time comprises r2114[0] (milliseconds) and r2114[1] (days).
After r2114[0] has reached a value of 86.400.000 ms (24 hours) this value is reset and r2114[1] is incremented.
Index:
[0] = Milliseconds
[1] = Days
Dependency:
Refer to: r0948, r2109, r2123, r2125, r2130, r2136, r2145, r2146
p2111
Alarm counter / Alarm counter
All objects
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1750, 8065
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
p2112
BI: External alarm 1 / External alarm 1
CU_CX32, CU_LINK,
CU_S, DMC20,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM54F_MA,
TM54F_SL
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p2112[0...n]
BI: External alarm 1 / External alarm 1
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2546
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
r2114[0...1]
System runtime / System runtime
CU_CX32, CU_S
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...