List of faults and alarms
Faults and Alarms
3-1515
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Reaction upon F:
A_INFEED: NONE (OFF1, OFF2)
VECTOR: NONE (OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
A05053 (F)
Parallel circuit: Inadmissible DC link voltage dissymmetry
Drive object:
A_INF, B_INF, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The deviation of the DC link voltage measured values exceeds the alarm threshold specified in p7011.
Remedy:
- inhibit the pulses of the faulted power unit (p7001).
- check the DC link connecting cables.
- the DC link voltage measurement is incorrect and must be calibrated or renewed.
Reaction upon F:
A_INFEED: NONE (OFF1, OFF2)
VECTOR: NONE (OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
A05054
Parallel circuit: Power unit de-activated
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the drive object involved, fewer power unit components connected in parallel are active than exist in the target
topology. Operation is only possible at reduced power (power de-rating).
Remedy:
Re-activate the de-activated power unit components.
See also: p0125 (Activate/de-activate power unit components), p0895 (Activate/de-activate power unit compo-
nents), p0897 (Parking axis selection)
F05055
Power circuit: Power units with different code numbers
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The code numbers of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different power unit code number was detected.
Remedy:
For parallel circuit configurations, only power units with identical power unit data may be used.
F05056
Parallel circuit: Power unit EPROM versions differ
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only power units with identical EEPROM versions may be used.
F05057
Parallel circuit: Power unit firmware versions differ
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the power modules connected in parallel do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only power modules with identical firmware versions may be used.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...