List of parameters
Parameters
1-455
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the limited field-generating current setpoint (Id_set).
This value comprises the steady-state field-generating current setpoint r1623 and a dynamic component that is only
set when changes are made to the flux setpoint.
Description:
Gain factor to weight the excitation current setpoint.
Description:
Displays the calculated excitation current setpoint.
Dependency:
Refer to: p0390
Description:
Displays the load angle of the current model.
Description:
Dynamic factor of the model controller in the current model
r1624
Field-generating current setpoint, total / Id_setp total
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6640, 6723,
6724, 6727
P-Group:
Displays, signals
Units group:
6_2
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1625[0...n]
Excitation current setpoint calibration / I_exc_setp cal
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6727
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
10.0 [%]
200.0 [%]
100.0 [%]
r1626
CO: Excitation current setpoint / I_exc_setp
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6727
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
r1627
CO: Current model load angle / I_mod load angle
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6727
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
- [°]
- [°]
- [°]
p1628[0...n]
Current model controller, dynamic factor / I_mod_ctr dyn_fact
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6727
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
1 [%]
400 [%]
50 [%]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...