Parameters
List of parameters
1-476
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the hysteresis for the changeover speed of the motor model for sensorless operation.
Dependency:
Refer to: p1755
Note:
The parameter value refers to p1755.
Description:
Sets the gain of the transient response controller when the motor model changes over from open-loop controlled
operation to closed-loop controlled operation.
Note:
Only for ASM and PSM in sensorless operation:
The settling range starts at 0.5 * p1755 * p1756.
For ASM it ends at p1755 * p1756 or at p1755, if p1759 is at the maximum value.
For PSM it always ends at p1755 * p1756.
Description:
Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled opera-
tion to open-loop controlled operation.
Dependency:
Refer to: p1755, p1756
Description:
Sets the minimum time for exceeding the changeover speed when changing from open-loop controlled operation to
closed-loop controlled operation.
Dependency:
Refer to: p1755, p1756
p1756
Motor model changeover speed hysteresis sensorless operation /
MotMod n_chgov hys
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.0 [%]
95.0 [%]
50.0 [%]
p1757[0...n]
Motor model w/o enc. op./cl.-loop controlled stab. controller Kp / MotMod w/o enc Kp
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
4
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL, FEM
Expert list:
1
Min Max
Factory
setting
0.01 10.00
0.70
p1758[0...n]
Motor model changeover delay time closed/open-loop control / MotMod t cl_op
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL, FEM
Expert list:
1
Min Max
Factory
setting
100 [ms]
10000 [ms]
1000 [ms]
p1759[0...n]
Motor model changeover delay time open/closed loop control / MotMod t op_cl
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL, FEM
Expert list:
1
Min Max
Factory
setting
0 [ms]
2000 [ms]
0 [ms]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...