Parameters
List of parameters
1-592
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Notice:
For p0322 = 0, the following applies: p2162 <= 0.1 * p0311
For p0322 > 0, the following applies: p1082 + p2162 <= 1.02 * p0322
If one of the conditions is violated, p2162 is appropriately and automatically reduced when exiting the commission-
ing mode.
Note:
For a negative velocity limit (r1087) the hysteresis is effective below the limit value and for a positive velocity limit
(r1084) above the limit value.
Description:
Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2164, p2166, r2197
Description:
Sets the velocity threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2164, p2166, r2197
Description:
Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" signal/mes-
sage (BO: r2197.7).
Dependency:
Refer to: p2163, p2166, r2197
Description:
Sets the hysteresis velocity (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" sig-
nal/message (BO: r2197.7).
p2163[0...n]
Speed threshold 4 / n_thresh val 4
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
210000.00 [RPM]
90.00 [RPM]
p2163[0...n]
Velocity threshold value 4 / v_thresh val 4
SERVO (Lin)
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [m/min]
1000.00 [m/min]
0.90 [m/min]
p2164[0...n]
Hysteresis speed 4 / n_hysteresis 4
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
200.00 [RPM]
2.00 [RPM]
p2164[0...n]
Hysteresis velocity 4 / v_hysteresis 4
SERVO (Lin)
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [m/min]
10.00 [m/min]
0.02 [m/min]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...