A02070
Trace: Parameter cannot be changed
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace parameter settings cannot be changed when the trace is active.
See also: p4700 (Trace control), p4710 (Trace trigger condition), p4711 (Trace trigger signal), p4712 (Trace trigger
threshold), p4713 (Trace tolerance band trigger threshold), p4714 (Trace tolerance band trigger threshold), p4715
(Trace bit mask trigger, bit mask), p4716 (Trace, bit mask trigger, trigger condition), p4720 (Trace recording cycle),
p4721 (Trace recording time), p4722 (Trace trigger delay), p4730 (Trace record signal 0), p4731 (Trace record signal
1), p4732 (Trace record signal 2), p4733 (Trace record signal 3), p4780 (Trace physical address signal 0), p4781
(Trace physical address signal 1), p4782 (Trace physical address signal 2), p4783 (Trace physical address signal
3), p4789 (Trace physical address trigger signal), p4795 (Trace memory bank changeover)
Remedy:
- stop the trace before parameterization.
- if required, start the trace.
A02075
Trace: Pretrigger time too long
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pretrigger time must be shorter than the recording time.
See also: p4721 (Trace recording time), p4722 (Trace trigger delay)
Remedy:
Check the pretrigger time setting and change if necessary.
F02080
Trace: Delete trace because units changed over
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The trace was cleared due to the fact that the units were changed over or the reference parameters changed.
Remedy:
A02099
Trace: Insufficient Control Unit memory
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory space still available on the Control Unit is no longer sufficient for the trace function.
Remedy:
Reduce the memory required, e.g. as follows:
- reduce the trace (record) time.
- increase the trace clock cycle.
- reduce the number of signals to be traced (recorded).
See also: r4708 (Trace memory space required), r4799 (Trace memory location free)
A02100
CU: Computation dead time current controller too short
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value in p0118 produces a dead time of one clock cycle because it lies before the setpoint becomes available.
A possible cause could be, for example, that the system characteristics no longer match those parameterized after
a component has been replaced.
Alarm value (r2134, floating point):
The minimum value for p0118 where a dead time no longer occurs.
Remedy:
- set p0118 to a value greater than or equal to the alarm value.
- set p0117 to an automatic setting.
- check the firmware releases of the components involved.
See also: p0117 (Current controller computation dead time mode), p0118 (Current controller computation dead
time)
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...