![Siemens SINAMICS S Series Скачать руководство пользователя страница 1031](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271031.webp)
List of parameters
Parameters
1-1031
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Number of safety messages that have occurred since the last reset.
Dependency:
The safety message buffer is cleared by resetting the parameter to 0.
Refer to: r9744, r9747, r9748, r9749, r9753, r9754, r9755, r9756, p9759
Note:
The parameter is reset to 0 at POWER ON.
Description:
Displays additional information about the safety message that has occurred for float values.
Dependency:
Refer to: r9744, r9747, r9748, r9749, p9752, r9754, r9755, r9756, p9759
Description:
Displays the relative system runtime in days when the safety message occurred.
Dependency:
Refer to: r9744, r9747, r9748, r9749, p9752, r9753, r9755, r9756, p9759
Description:
Displays the relative system runtime in milliseconds when the safety message was removed.
Dependency:
Refer to: r9744, r9747, r9748, r9749, p9752, r9753, r9754, r9756, p9759
Description:
Displays the relative system runtime in days when the safety message was removed.
p9752
SI message cases, counter / SI msg_cases count
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
r9753[0...63]
SI message value for float values / SI msg_val float
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r9754[0...63]
SI message time received in days / SI t_msg recv days
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r9755[0...63]
SI message time removed in milliseconds / SI t_msg rem ms
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
r9756[0...63]
SI message time removed in days / SI t_msg rem days
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...