List of parameters
Parameters
1-359
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the response for the Vdc_min controller (kinetic buffering).
Values:
0:
Buffer Vdc until undervoltage, n<p1257 -> F07405
1:
Buff. Vdc until undervolt., n<p1257 -> F07405, t>p1255 -> F07406
Dependency:
Refer to: F07405, F07406
Description:
Sets the speed threshold for the Vdc-min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
Note:
The regenerative power limit p1531 is used for vector control to pre-control the Vdc_max controller. The lower the
power limit is set, the lower the correction signals of the controller when the voltage limit is reached.
Description:
Selecting the bypass functionality.
Values:
0:
Bypass function de-activated
1:
Bypass with synchronization and overlap
2:
Bypass with synchronization without overlap
3:
Bypass without synchronization
Dependency:
The bypass functionality is enabled together with the function module "technology controller (r0108.16).
For p1260 = 2 (bypass with synchronization without overlap) and p1260 = 3 (bypass without synchronization), then
the "flying restart" function must be activated (p1200).
p1256[0...n]
Vdc_min controller response (kinetic buffering) / Vdc_min response
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0 1
0
p1257[0...n]
Vdc_min controller speed threshold / Vdc_min n_thresh
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Functions
Units group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.0 [RPM]
210000.0 [RPM]
50.0 [RPM]
r1258
CO: Vdc controller output / Vdc_ctrl output
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6220
P-Group:
Functions
Units group:
6_2
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1260
Bypass configuration / Bypass config
VECTOR (Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...