Parameters
List of parameters
1-360
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
If the bypass function is selected ((p1260 > 0), then when the power unit restarts after POWER OFF, the state of
the bypass switch is evaluated. This means that after the ramp-up, it is possible to directly change into the standby
mode. This is only possible for p1267 = 0 (bypass using the control signal) and if the control command after the sys-
tem has been motor is still available (p1266). This function has a high priority than the automatic restart function
(p1210).
The bypass function can only be switched-out again (p1260 = 0) if the bypass is not active or the bypass function
has a fault.
Description:
Control and feedback signals of the bypass switch.
Dependency:
Refer to: p2369
Note:
Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder
cables should be controlled. These should be selected/dimensioned for switching under load.
Description:
Sets the dead time for non-synchronized bypass.
Note:
This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-magne-
tization time of the motor (p0347).
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
r1261.0...9
CO/BO: Bypass control/status word / Bypass STW / ZSW
VECTOR (Tech_ctrl)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Command switch motor - drive
Close
Open
-
01
Command switch motor - line supply
Close
Open
-
02
Synchronization requested
Yes
No
-
03
Staging status
Active
Not active
-
05
Feedback signal switch motor - drive
Closed
Opened
-
06
Feedback signal switch motor - line supply
Closed
Opened
-
07
Bypass command (from p1266)
Yes
No
-
08
Feedback signal synchronization completed
(from p1268)
Yes
No
-
09
Staging requested (from p2369)
Yes
No
-
p1262[0...n]
Bypass dead time / Bypass t_dead
VECTOR (Tech_ctrl)
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
20.000 [s]
1.000 [s]
p1263
Debypass delay time / Debypass t_del
VECTOR (Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
300.000 [s]
1.000 [s]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...