Description:
Operating display for the drive.
Values:
0:
[00] Operation - everything enabled
10:
[10] Operation - set "enable setpoint" = "1" (p1142, p1152)
11:
[11] Operation - set "enable speed controller" = "1" (p0856)
12:
[12] Operation - RFG frozen, set "RFG start" = "1" (p1141)
13:
[13] Operation - set "enable RFG" = "1" (p1140)
14:
[14] Oper. - MotID, excit. running and/or brake opens, SS2, SOS
15:
[15] Operation - open brake (p1215)
16:
[16] Oper - withdraw braking w/ OFF1 using "ON/OFF1" = "1"
17:
[17] Oper - braking w/ OFF3 can only be interrupted w/ OFF2
18:
[18] Operation - brake on fault remove fault acknowledge
19:
[19] Operation - armature short-circuit active (p1230, p1231)
21:
[21] Ready - set "enable operation" = "1" (p0852)
22:
[22] Ready - de-magnetization running (p0347)
23:
[23] Ready - set "infeed operation" = "1" (p0864)
31:
[31] Ready to power-up - set "ON/OFF1" = "0/1" (p0840)
41:
[41] Power-on inhibit - set "ON/OFF1" = "0" (p0840)
42:
[42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845)
43:
[43] Power-on inhibit - set "OC/OFF3" = "1" (p0848, p0849)
44:
[44] Power-on inhibit - connect 24 V to terminal EP (hardware)
45:
[45] Power-on inhib - remove fault cause, acknowledge fault
46:
[46] Power-on inhibit - exit comm mode (p0009, p0010)
60:
[60] Infeed de-activated/not operational
250:
[250] Device signals a topology error
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
SOS: Safe Operating Stop
Description:
Operating display for the infeed.
Values:
0:
[00] Operation - everything enabled
31:
[31] Rdy to power-up - pre-chrg running (p0857)
32:
[32] Ready to power-up - set "ON/OFF1" = "0/1" (p0840)
41:
[41] Power-on inhibit - set "ON/OFF1" = "0" (p0840)
42:
[42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845)
44:
[44] Power-on inhibit - connect 24 V to terminal EP (hardware)
45:
[45] Power-on inhib - remove fault cause, acknowledge fault
r0002
Drive operating display / Drv op_display
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 250
-
r0002
Infeed operating display / INF op_display
B_INF
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 250
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...