Parameters
List of parameters
1-494
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: p1910, r1912, r1913, r1915, r1925, r1927, r1932, r1933, r1934, r1935, r1936, r1950, r1951, p1952, p1953
Note:
For an induction motor (ASM), the following bits are effective: 8, 9, 10, 13
For a synchronous motor (SRM), the following bits are effective: 8, 9, 13, 14
Re bit 14:
- after successfully determining the voltage emulation error, the display of the phase voltage actual values r0089
and the active power actual value r0082 and the torque actual value r0080 are significantly more accurate.
- the voltage emulation errors should be identified with the Motor Module in the warm state.
- the motor temperature (r0035) should not change significantly (i.e. it should not be identified immediately after a
load duty cycle).
Description:
Sets the configuration of the motor data identification.
Note:
Note for PEM:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature induc-
tance Lq are measured at a low current.
When de-selecting with bit 11 or in the V/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
08
Measure D inductance
Yes
No
-
09
Measure Q inductance
Yes
No
-
10
Magnetizing field inductance and measure
rotor resistance
Yes
No
-
13
Measure commutation angle and direction
of rotation
Yes
No
-
14
Determining the voltage emulation error
Yes
No
-
p1909[0...n]
Motor data identification control word / MotID STW
VECTOR
Can be changed:
T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Unsigned16
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Stator inductance estimate no measure-
ment
Yes
No
-
01
Cl.-loop current control w/ dead-beat con-
troller
Yes
No
-
02
Rotor time constant estimate no measure-
ment
Yes
No
-
03
Leakage inductance estimate no measure-
ment
Yes
No
-
04
Activates the identification dynamic leak-
age inductance
Yes
No
-
05
Determine Tr and Lsig evaluation in the time
range
Yes
No
-
06
Activates vibration damping
Yes
No
-
07
De-activates the vibration detection
Yes
No
-
11
De-activate pulse measurement Lq Ld
Yes
No
-
12
De-activate rotor resistance Rr measure-
ment
Yes
No
-
15
Only measure stator resistance and valve
voltage error
Yes
No
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...