List of parameters
Parameters
1-677
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
Re bit 02:
The "referencing active" signal is an OR logic operation of "search for reference active" and "flying referencing
active".
Re bit 00 ... 07 and 11 ... 14:
These signals are generated in the function module "basic positioner".
Re bit 08:
The signal is generated in the "closed-loop position control" function module.
Description:
Displays the corrective value for the position actual value.
Dependency:
Refer to: r2684
Note:
As standard, the following BICO interconnection is established: CI: p2513 = r2685
Using this value, e.g. modulo corrections are carried out.
Description:
Displays the effective torque limiting.
r2686[0]: Displays the effective upper torque limiting when traversing to fixed stop (referred to CI: p1522, CI:
p1523).
r2686[1]: Displays the effective lower torque limiting when traversing to fixed stop (referred to CI: p1522, CI:
p1523).
Dependency:
Refer to: p1520, p1521, p1522, p1523, r2676
Note:
As standard, the following BICO interconnections are established:
CI: p1528 = r2686[0]
CI: p1529 = r2686[1]
Description:
Displays the effective torque setpoint when reaching the fixed stop (referred to CI: p1522, CI: p1523).
Dependency:
Refer to: p1520, p1521, p1522, p1523, r2676
12
Acknowledgement, traversing block acti-
vated
Yes
No
3616,
3620
13
STOP cam minus active
Yes
No
3630
14
STOP cam plus active
Yes
No
3630
15
Traversing command active
Yes
No
3635
r2685
CO: EPOS corrective value / Corrective value
SERVO (EPOS),
VECTOR (EPOS)
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Integer32
Dynamic index:
-
Func. diagram:
3635
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [LU]
- [LU]
- [LU]
r2686[0...1]
CO: EPOS torque limiting effective / M_limit eff
SERVO (EPOS),
VECTOR (EPOS)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
3616, 3617
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
r2687
CO: EPOS torque setpoint / M_set
SERVO (EPOS),
VECTOR (EPOS)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
3616, 3617
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...