Parameters
List of parameters
1-124
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the status word of the cooling system.
Dependency:
Refer to: p0266
Description:
Sets the absolute value by which the threshold to initiate the undervoltage fault (F30003) is reduced.
Dependency:
Refer to: p0210, r0296
Refer to: F30003
Notice:
When using a Control Supply Module (CSM) for 24 V supply from the DC link, the minimum continuous DC link volt-
age may not lie below 430 V. DC link voltages in the range 300 ... 430 V are permissible up to a duration of 1 min.
Note:
The resulting shutdown threshold can be read in r0296 and is dependent on the selected rated voltage (p0210) and
the power unit being used.
Description:
Sets the voltage threshold to initiate alarm A06810.
The value represents an offset so that the alarm threshold is obtained from the sum of r0296 and p0279.
Dependency:
Refer to: p0210, r0296
Refer to: A06810
Note:
The absolute value of the alarm threshold depends on the selected unit supply voltage (p0210).
r0267.0...7
BO: Cooling system status word / RKA ZSW
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
RKA powered-up
Yes
No
-
01
RKA ready to be powered-up
Yes
No
-
02
RKA no alarm present
Yes
No
-
03
RKA no fault present
Yes
No
-
04
RKA no leaked fluid
Yes
No
-
05
RKA liquid flow OK
Yes
No
-
06
RKA conductivity, no fault
Yes
No
9974
07
RKA conductivity, no alarm
Yes
No
9974
p0278
DC link voltage undervoltage threshold reduction / Vdc V_under red
SERVO, VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-80 [V]
0 [V]
0 [V]
p0279
DC link voltage offset alarm threshold / Vdc offs A thresh
A_INF, B_INF,
S_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8760, 8864,
8964
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 [V]
100 [V]
0 [V]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...