Parameters
List of parameters
1-442
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source to activate/de-activate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
When traveling to fixed stop, the fault F07900 "motor blocked" is suppressed.
When the function module "position positioner" (r0108.4 = 1) is activated, this binector input is interconnected as
follows as standard:
BI: p1545 = r2683.14
Description:
Sets the speed threshold for the motoring/regenerating limit.
For speeds where the absolute value is less than p1546, then the following applies:
- For p1400.13 = 0: Motoring limit (speed threshold is compared to the speed actual value).
- For p1400.13 = 1: Regenerative limiting (speed threshold is compared to the speed setpoint).
Description:
Sets the velocity threshold for the motoring/regenerating limit.
For velocities where the absolute value is less than p1546, then the following applies:
- For p1400.13 = 0: Motoring limit (velocity threshold is compared to the velocity actual value).
- For p1400.13 = 1: Regenerative limiting (velocity threshold is compared to the velocity setpoint).
Description:
Displays the torque limit to limit the speed controller output.
Index:
[0] = Upper limit
[1] = Lower limit
p1545[0...n]
BI: Activates travel to a fixed stop / TfS activation
VECTOR (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2520, 3617
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
0
p1546
Speed threshold motoring/regenerating / n_thresh mot/regen
SERVO
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [RPM]
210000.0 [RPM]
20.0 [RPM]
p1546
Velocity threshold motoring/regenerating / v_thresh mot/regen
SERVO (Lin)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [m/min]
1000.0 [m/min]
0.2 [m/min]
r1547[0...1]
CO: Torque limit for speed controller output / M_max outp n_ctrl
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
7_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...