Parameters
List of parameters
1-38
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values:
0:
Ready
1:
Device configuration
2:
Defining the drive type/function module
3:
Drive basis configuration
4:
Data set basis configuration
29:
Device download
30:
Parameter reset
50:
OA application configuration
Note:
The drives can only be powered-up outside the device commissioning (the inverter enabled). In this case, p0009
must be 0 (Ready) and the individual drive objects must have already gone into operation (p0010).
p0009 = 1: Device configuration
At the first commissioning of the devices, after booting, the device is in the "device configuration" state. To start the
internal automatic first commissioning of the drive unit, p0009 should be set to 0 (Ready) after the ID for the actual
topology (r0098) was transferred into the ID for the target topology (p0099). To do this, it is sufficient to set a single
index value of p0099[x] the same as r0098[x]. Before the device has been completely commissioned, no other
parameter can be changed. After the first commissioning was carried out, in this state, when required, other basic
device configuration parameters can be adapted (e.g. the basic sampling time in p0110).
p0009 = 2: Defines the drive type / function module
In this state, the drive object types and/or the function modules can be changed or selected for the individual drive
objects. To do this, the drive object type can be set using p0107[0...15] and the function can be set using
p0108[0...15] (refer to p0101[0...15]).
p0009 = 3: Drive basis configuration
In this state, after the device has been commissioned for the first time, basic changes can be made for the individ-
ual drive objects (e.g. sampling times in p0111, p0112, p0115 and the number of data sets in p0120, p0130, p0140,
p0170, p0180).
p0009 = 4: Data set basis configuration
In this state, after the device has been commissioned for the first time, for the individual drive objects changes can
be made regarding the assignment of the components (p0121, p0131, p0141, p0151, p0161) to the individual data
sets and the assignment of the power unit, motor and encoder to the drive data sets (p0185, ...).
p0009 = 29: Device download
If a download is made using the commissioning software, the device is automatically brought into this state. After
the download has been completed, p0009 is automatically set to 0 (ready). It is not possible to manually set p0009
to this value.
p0009 = 30: Parameter reset
In order to bring the complete unit into the "first commissioning" state or to load the parameters saved using p0977,
to start, p0009 must be set to this value. p0976 can then be changed to the required value.
p0009 = 50: OEM application configuration
In this state, after the device has been commissioned for the first time, changes can be made for the individual drive
objects regarding the activity (p4956) of the OEM applications.
Description:
Sets the parameter filter to commission an infeed unit.
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
Values:
0:
Ready
1:
Quick commissioning
2:
Power unit commissioning
5:
Technological application/units
29:
Download
30:
Parameter reset
Note:
The drive can only be powered-up outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
p0010
Infeed commissioning parameter filter / INF comm par_filt
A_INF, B_INF,
S_INF
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 30
1
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...