List of parameters
Parameters
1-55
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the smoothed actual power factor.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as process quantity and may only be used as display quantity.
Significance for the motor: Motor power factor
Significance for the infeed: Power factor at the connection point (p3470, p3471)
Description:
Sets the smoothing time constant for the following display values:
SERVO: r0078[1], r0079[1], r0081 (calculated from the quantities smoothed with p0045), r0082[1].
VECTOR: r0063[1], r0068[1], r0080[1], r0082[1].
Description:
Displays missing enable signals that are preventing the closed-loop infeed control from being commissioned.
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for the infeed are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a power-on inhibit.
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
r0038
Power factor smoothed / Cos phi smooth
A_INF, S_INF, VEC-
TOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6799, 8850,
8950
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p0045
Smoothing time constant, display values / T_smth display
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
4715, 5610,
5730, 6714, 8012
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
200.00 [ms]
1.00 [ms]
r0046.0...29
CO/BO: Missing enable sig / Missing enable sig
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
8834, 8934
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
-
01
OFF2 enable missing
Yes
No
-
03
Enable operation missing
Yes
No
-
08
EP terminals enable missing
Yes
No
-
16
OFF1 enable internal missing
Yes
No
-
17
OFF2 enable internal missing
Yes
No
-
19
Pulse enable internal missing
Yes
No
-
26
Infeed inactive or not operational
Yes
No
-
29
Cooling system ready signal missing
Yes
No
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...