![Siemens SINAMICS S Series Скачать руководство пользователя страница 1043](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271043.webp)
List of parameters
Parameters
1-1043
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Enters the number of the component where the setting of how the actual topology should be compared to the target
topology should be changed.
Dependency:
Refer to: p9908
Description:
Sets the type of comparison of a component in the target topology with the actual topology.
The comparison is started by setting the required value.
Values:
0:
High: Compares the complete electronic rating plate
1:
Average: Compares the component type and the Order number
2:
Low: Compares the component type
3:
Minimum: Compares the component class
99:
Topology has different comparison stages
Dependency:
Refer to: p9907
Note:
The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9908 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9908 = 1: Component type, Order No.
p9908 = 2: Component type
p9908 = 3: Component class (e.g. Sensor Module or Motor Module)
Description:
For p9909 = 1, the serial number and the hardware version of the new replaced component is automatically trans-
ferred from the actual topology into the target topology and then saved in a non-volatile fashion.
For the components that have been replaced, the electronic type plate must match as far as the following data is
concerned:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
p9907
Topology comparison, comparison stage of the component number /
Topo_cmpr comp_no
CU_CX32, CU_S
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
-
P-Group:
Topology
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 199
0
p9908
Topology comparison, comparison stage of a component / Topo_cmpr 1 comp
CU_CX32, CU_S
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Topology
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 99
0
p9909
Topology comparison, component replacement / Topo_cmpr replace
CU_CX32, CU_S
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
-
P-Group:
Topology
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
1
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...