List of faults and alarms
Faults and Alarms
3-1527
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy:
- reduce the temperature at the sensor.
- check the temperature sensor connection.
F06908
Braking Module internal shutdown due to overtemperature
Drive object:
B_INF
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
Shutdown of the Braking Module due to overtemperature at the temperature sensor of the braking resistor for more
than 60s.
See also: r3688 (Digital Braking Module fault overtemperature)
Remedy:
- reduce the temperature at the sensor.
- check the temperature sensor connection.
F06909
Braking Module internal Vce fault
Drive object:
B_INF
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Trip due to Vce fault. Collector emitter voltage dip (Vce)
See also: r3689 (Digital Braking Module Vce fault)
Remedy:
- Power ON
- replace the unit.
F07011
Drive: Motor overtemperature
Drive object:
SERVO, VECTOR
Reaction:
OFF2 (NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
KTY:
The motor temperature has exceeded the fault threshold (p0605) or the timer stage (p0606) after the alarm threshold
was exceeded (p0604) has expired.
VECTOR: The response parameterized in p0610 becomes active.
PTC:
The response threshold of 1650 Ohm was exceeded and the timer stage (p0606) has expired.
VECTOR: The response parameterized in p0610 becomes active.
Possible causes:
- motor is overloaded.
- motor ambient temperature too high.
- wire breakage or sensor not connected
Fault value (r0949, interpret decimal):
For SME selected (p0601 = 10), number of the sensor channel leading to the message.
See also: p0604 (Motor overtemperature alarm threshold), p0605 (Motor overtemperature fault threshold), p0606
(Motor overtemperature timer), p0610 (Motor overtemperature response)
Remedy:
- reduce the motor load.
- check the ambient temperature.
- check the wiring and sensor connector.
See also: p0604 (Motor overtemperature alarm threshold), p0605 (Motor overtemperature fault threshold), p0606
(Motor overtemperature timer)
A07015
Drive: Motor temperature sensor alarm
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected when evaluating the temperature sensor set in p0600 and p0601.
With the fault, the time in p0607 is started. If the fault is still present after this time has expired, then fault F07016 is
output; however, at the earliest, 1 s after alarm A07015.
Possible causes:
- wire breakage or sensor not connected (KTY: R > 1630 Ohm).
- measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).
Alarm value (r2124, interpret decimal):
For SME selected (p0601 = 10), number of the sensor channel leading to the message.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...