Parameters
List of parameters
1-160
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the saturated magnetizing inductance of the separately-excited synchronous motor quadrature to the rotor
direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 1st value pair of the characteristic.
Sets the first flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0366
Note:
For induction motors, p0362 = 100 % corresponds to the rated motor flux.
For separately-excited synchronous motors p0362 = 100% corresponds to an induced terminal voltage with the
magnitude of the rated motor voltage (under no-load conditions at the synchronous speed).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 2nd value pair of the characteristic.
Sets the second flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0367
Note:
For induction motors, p0363 = 100 % corresponds to the rated motor flux.
For separately-excited synchronous motors p0363 = 100% corresponds to an induced terminal voltage with the
magnitude of the rated motor voltage (under no-load conditions at the synchronous speed).
p0361[0...n]
Motor magnetizing inductance q axis, saturated / Mot L_magn q sat
VECTOR
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_EQU
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
15_1
Unit selection:
p0349
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.00000 [mH]
10000.00000 [mH]
0.00000 [mH]
p0362[0...n]
Saturation characteristic flux 1 / Mot saturat.flux 1
VECTOR
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
PEM
Expert list:
1
Min Max
Factory
setting
10.0 [%]
300.0 [%]
60.0 [%]
p0363[0...n]
Saturation characteristic flux 2 / Mot saturat.flux 2
VECTOR
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
PEM
Expert list:
1
Min Max
Factory
setting
10.0 [%]
300.0 [%]
85.0 [%]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...