Parameters
List of parameters
1-420
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the scaling for the acceleration integrator at low speeds (only for sensorless torque control).
Dependency:
Refer to: p0341, p0342
Description:
Runs the appropriate ACX file on the CompactFlash card.
The Connector Inputs (CI) for the torque setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected ACX file must be located in the following directory:
... /PMACROS/<drive object>/P1500/PMxxxxxx.ACX
Example:
p1500 = 6 --> the file PM000006.ACX is run.
Dependency:
The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc-
tory intended on the CompactFlash card.
Refer to: p0015, p0700, p1000, r8573
Notice:
No errors were issued during fast commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
Note:
The macros in the specified directory are displayed in r8573. r8573 is not in the Expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
CI: Connector Input
Description:
Runs the appropriate ACX file on the CompactFlash card.
The Connector Inputs (CI) for the torque setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected ACX file must be located in the following directory:
... /PMACROS/<drive object>/P1500/PMxxxxxx.ACX
Example:
p1500 = 6 --> the file PM000006.ACX is run.
Dependency:
The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc-
tory intended on the CompactFlash card.
Refer to: p0015, p0700, p1000, r8573
Notice:
No errors were issued during fast commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
p1499[0...n]
Accelerating for torque control, scaling / a for M_ctrl scal
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.0 [%]
400.0 [%]
100.0 [%]
p1500[0...n]
Macro Connector Inputs (CI) for torque setpoints / Macro CI M_set
SERVO, VECTOR
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
CDS, p0170
Func. diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0 999999
0
p1500[0...n]
Macro Connector Inputs (CI) for force setpoints / Macro CI F_set
SERVO (Lin)
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
CDS, p0170
Func. diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0 999999
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...